Gas-turbine power stations PAES-2500, -2500B and EG-2500

HIGH VOLTAGE SWITCHGEAR MET

TECHNICAL DATA

Rated voltage, V ....................................................................................................... 13800

Maximum operating voltage, V ................................................................................... 15000

Rated current of switchgear cabinet, A ....................................................................... 630

Rated current of circuit breaker, not more than, kA ..................................................... 18

Power transformer capacity, kV·A .............................................................................. 25

Insulation level ........................................................................................................ Ã

Control rated voltage, V ........................................................................................... 24

Total mass of switchgear cabinets, kg ........................................................................ 1220

CONTROL BOARD

The control board serves to control the main engine, turbo-generator plant TGU-8, high voltage equipment, ancillary systems, as well as to regulate parameters of electric power generating unit and its auxilary systems.

The board is made as a separate unit and installed in the operator’s room.

MOTOR HEATER MP-70

The heater is included into the delivery set and intended to preheat the power generating unit equipment before starting under the winter conditions of operation.

SYSTEMS PROVIDING POWER GENERATING
UNIT OPERATION

The power generating unit is equipped with the following systems which are necessary for independent operation:

Lubricating and breathing system

Fuel supply system

Automatic control and monitoring system

Starting system

Cooling and ventilating system

Noise suppressing system

The systems of heating, electric power supply and others

DELIVERY SET

The set includes:

The semitrailer-van with the whole power generating unit equipment

Engine inlet noise suppressor

Engine exhaust noise suppressor

Set of tools and devices for the technical servicing of the entire power generating unit equipment

Set of power generating unit spare parts including the spare parts for the entire power generating unit equipment

Set of operation and maintenance publications

DELIVERY SET

The set includes the turbo-generator container complete with the inlet noise suppressor and the power generating unit facilities providing for the engine and generator operation;

Exhaust noise suppressor;

Operator’s room with the cabinets for high voltage switchgear and control board;

Set of tools and appliances for servicing the entire power generating unit equipment;

Set of spare parts of the power generating unit equipment including spares for power generating unit equipment;

Set of operation and maintenance publications.

TRANSPORTATION

The above power generating units are shipped by road, rail, water and air transport.

All cargo units are made according to the international standard clearance limits and are provided with mooring devices.

IN-SERVICE MAINTENANCE

MANUFACTURER’S SERVICE IS REPRESENTED BY:

— in-time delivery of the blocks and accessories instead of those which completed their service life;

— operation servicing on the ‘on condition’ basis;

— theoretical and practical training of customer’s specialists at the manufacturing plant or under the field conditions at any point of the world; the information obtained by the customer’s specialists prevents from making mistakes when servicing our equipment;

— providing a spare engine to the customer to ensure the continuous functioning of the power generating unit during overhaul of the customer’s engine.

— sending manufacturer’s specialists to the customer for the time of power generating unit starting and, if necessary, for any time of operation.

IN-SERVICE MAINTENANCE

LOW OPERATION EXPENSES DUE TO:

— minimum capital expenditure for the operating site, fuel supply, electric energy reception;

— low cost maintenance;

— power self-supplying;

— long service life;

— high operation reliability;

— insignificant irretrievable oil losses;

— high level of equipment serviceability

HIGH SERVICEABILITY DUE TO:

— an easy access to the places of checking and adjustment;

— remote monitoring and diagnosis of the power generating unit equipment condition;

— a speedy trouble eliminating through availability of necessary tooling and appropriate spare parts set.

REPAIR SERVICING

— is supervised by the manufacturer

— the manufacturer provides for supply of the appropriate blocks and other equipment items for the running repair

— anticipates that the engine overhaul is performed at the manufacturing plant after which the original overhaul life is assigned

— proceeds from the manufacturer’s willingness to cooperate with the companies which wish to create their own repair facilities

GAS-TURBINE ENGINES OF AI-20 FAMILY

GAS-TURBINE ENGINES OF AI-20 FAMILY

ENGINE FAMILY
TO DRIVE POWER GENERATING UNIT GENERATOR
OF 2.5 MW POWER AND CURRENT FREQUENCY OF:

50 Hz
rotational speed, min-1:
of rotor - 12300+90
of output shaft - 1000
60 Hz
rotational speed, min-1:
of rotor - 12240-90
of output shaft - 1200
AI-20DMNAI-20DME
to operate on liquid fuelto operate on gaseous fuel
AI-20DMNChAI-20DMECh
to operate on liquid fuelto operate on gaseous fuel

GAS-TURBINE ENGINES OF AI-20 FAMILY TECHNICAL CHARACTERISTICS

INDICES AI-20DMN
AI-20DMNCh
AI-20DME
AI-20DMECh
Engine type gas-turbine
Version general climatic
Fuel type kerosene,
diesel fuel
natural or
casing-head gas
Lubrication type circulating, forced-feed
Power at engine operation conditions depending on power generating unit
generator load, kW:
— idle power condition 0
— 0.5 nominal 1250
— nominal 2500
— overload 2750
Fuel consumption at nominal conditions, kg/h, not more than 995 836
Specific fuel consumption at nominal conditions, kg/kW·h, not more than 0.398 0.334

1 | 2 | 3 | 4 | 5 | 6 | 7