Gas-turbine power stations PAES-2500, -2500B and EG-2500

ELECTRICAL ENERGY QUALITY INDICES

In the steady state thermal condition at the invariable balanced load:

the steady state voltage deviation, % ....................................................................................... ±1

the steady state frequency deviation, %.................................................................................... ±1

At 50 % shedding/surging of the load:

transient voltage deviation, %.................................................................................................. ±6

transient frequency deviation, % ............................................................................................. ±7

The duration of transient process of restoring the frequency and voltage
(over the preset range) at 50 % shedding/surging of the load,
s, not more than .................................................................................................................... 5

CHARACTERISTICS
Power versus altitude above sea level
at air temperature of 15°C

CHARACTERISTICS

Power versus temperature at pressure of 96 kPà (PSI-14.7)

CHARACTERISTICS

Gaseous fuel flow rate versus output shaft power
(lower fuel calorific value of 50000 kJ/kg, ISA)

ECOLOGICAL INDICES

The equivalent noise level at 1 m distance from the power generating unit contour does not exceed 85 dB (A).

The content of noxious substances in exhaust gases when operating at the rated load equals:

Ecological parameter AI-20DIE and AI-20DIECh (gaseous fuel) AI-20DIN and AI-20DINCh (liquid fuel)
Nitrogen oxides, NOx, 15 % O2 91 mg/m3 (44.4 ppm) 141 mg/m3 (68.8 ppm)
Carbon oxide, CO, 15 % O2 107 mg/m3 (85.6 ppm) 215 mg/m3 (172 ppm)